INT89 U Diagnose

Article-Nr.: 22 A 637 S021

Downloads

English
INT89 U Diagnose

Productdetails

Application Extended service life of system due to temperature and current monitoring
Supply voltage AC 115-240V
Permitted ambient temperature -30...+70°C
Reset delay: Overvoltage 1min ±6s
Reset of reset delay Main reset >5s only possible if there is no error current
Relay: Connection 240V ~ 2.5A C300Min. 24V ~ / 20mA
Relay: Mechanical service life Approx. 1 million switching cycles
Interface Diagnose port (DP)
Protection class acc. To EN 60529 IP00
Connection type 6.3mm flat plugs
Housing material PA glass-fibre-reinforced
Mounting Screw mounted
Dimensions See dimensions in mm
Weight Approx. 200g
Check base EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2
Mains voltage monitoring: Monitoring range 1 AC 110-120V
Mains voltage monitoring: Monitoring range 1, Mains voltage recognition ≤150V
Mains voltage monitoring: Monitoring range 1, Accuracy ±5% of the measuring range
Mains voltage monitoring: Monitoring range 1, Undervoltage preliminary warning <103V
Mains voltage monitoring: Monitoring range 1, Undervoltage shutdown <98V
Mains voltage monitoring: Monitoring range 1, Overvoltage preliminary warning >127V
Mains voltage monitoring: Monitoring range 1, Overvoltage shutdown >132V
Mains voltage monitoring: Monitoring range 2 AC 220-240V
Mains voltage monitoring: Monitoring range 2, Mains voltage recognition >150V
Mains voltage monitoring: Monitoring range 2, Accuracy ±5% of the measuring range
Mains voltage monitoring: Monitoring range 2, Undervoltage preliminary warning <187V
Mains voltage monitoring: Monitoring range 2, Undervoltage shutdown <177V
Mains voltage monitoring: Monitoring range 2, Overvoltage preliminary warning >244V
Mains voltage monitoring: Monitoring range 2, Overvoltage shutdown >265V
Reset delay: Undervoltage 1min ±6s