INT69 YL Diagnose

Article-Nr.: 25 A 497

Downloads

English
INT69 YL Diagnose

Productdetails

Application Compressors with direction of rotation essential for function and oil management
Functions Motor temperature static, Motor temperature dynamic, Oil temperature, Short circuit, short cycling, Phase monitoring, phase sequence, phase asymmetry, Lock-out, operating recognition
Supply voltage AC/DC 24-240V
Permitted ambient temperature -30...+70°C
Temperature measuring circuits: Type 1-2 AMS sensors in series alternative 1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series
Temperature measuring circuits: R_25, total <1.8kΩ
Temperature measuring circuits: R_trip, static 4.5kΩ ±20%
Temperature measuring circuits: R_reset 2.75kΩ ±20%
Temperature measuring circuits: Max. length connection line 30m
Short circuit monitoring system PTC Typically <30Ω
Input oil flow oil level and oil filter soiling: Designed for Potential-free normally open contact (typ. 3.3V, 1mA)
Input oil flow oil level and oil filter soiling: Max. length connection line 30m
Motor voltage 3 AC 20-100Hz 80-690V ±10%
Phase monitoring: Phase sequence Active about 1s after motor start for about 5s
Phase monitoring: Phase failure Active about 1s after the motor start until the motor stop
Phase monitoring: Inactive After motor stop for approx. 10s
Phase monitoring: Phase asymmetry Active about 1s after the motor start until the motor stop
Switching frequency overstepping 3 switch-offs in 60s or 10 switch-offs in 1h
Operating with frequency converters Suitable
Reset delay: Motor temperature static 5min ±1min
Reset delay: Motor temperature dynamic 10min ±2min, 60min ±12min, Locked
Reset delay: Switching frequency overstepping 5min ±1min, 30min ±6min
Reset delay: Incorrect phase sequence Locked
Reset delay: Oil temperature Undelayed
Reset delay: Phase asymmetry 5min ±1min, Verriegelt
Reset delay: Oil flow 5min ±1min, Verriegelt
Reset delay: Oil filter Locked
Reset delay: Oil level Locked
Resetting the lock or the reset delay Main reset >5s or reset by keyboard only possible if there is no error current
External button: Designed for Potential-free normally open contact (typ. 3.3V, 1mA)
External button: Max. length connection line 1m
Relay: Connection AC 240V 2.5A C300 at least AC/DC 24V 20mA
Relay: Mechanical service life Approx. 1 million switching cycles
Interface Diagnose port (DP)
Protection class acc. To EN 60529 IP00
Connection type 6.3mm flat plugs (L1-L3, L and N), push-in spring terminals, 0.25-0.75mm2
Housing material PA glass-fibre-reinforced
Mounting Screw mounted
Dimensions Refer to dimensions in mm
Weight Approx. 150g
Check base EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2
Approval UL File No. E75899 cURus

Cookies facilitate the provision of services on this website. By using this website, you agree to the use of cookies. Privacy policy.